Chapter 4 Parameters
4-94
Settings Function Description
14 External
Fault
Parameter value 14 programs one of the Multi-function Input
Terminals MI3~MI6 (Pr.04.05~Pr.04.08) to be External Fault
(E.F.) inputs.
ON
MI -GND
x
ON
OFF
ON
Reset
ON
OFF
voltage
frequency
setting
frequency
Time
operation
command
15
PID function
disabled
When an input ON with this setting is ON, the PID function will be
disabled.
16 Output
Shutoff
Stop
AC motor drive will stop output and the motor free run if one of
these settings is enabled. If the status of terminal is changed, AC
motor drive will restart from 0Hz.
ON
MI -GND
x
ON
OF F
ON
voltage
frequency
setting
frequency
Time
operation
command
17
Parameter lock
enable
When this setting is enabled, all parameters will be locked and
write parameters is disabled.