Chapter 4 Parameters
4-6
Parameter Explanation
Settings
Factory
Setting
Customer
01.33
Maximum Output
Voltage (Vmax)
(Motor 2)
115V/230V series: 0.1V to 255.0V
220.0
460V series: 0.1V to 510.0V
440.0
01.34
Mid-Point
Frequency (Fmid)
(Motor 2)
0
.10 to 599.00 Hz
1.50
01.35
Mid-Point Voltage
(Vmid) (Motor 2)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.36
Minimum Output
Frequency (Fmin)
(Motor 2)
0.
10 to 599.00 Hz
1.50
01.37
Minimum Output
Voltage (Vmin)
(Motor 2)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.38
Maximum Voltage
Frequency (Fbase)
(Motor 3)
0.10 to 599.00 Hz
60.00
01.39
Maximum Output
Voltage (Vmax)
(Motor 3)
115V/230V series: 0.1V to 255.0V
220.0
460V series: 0.1V to 510.0V
440.0
01.40
Mid-Point
Frequency (Fmid)
(Motor 3)
0
.10 to 599.00 Hz
1.50
01.41
Mid-Point Voltage
(Vmid) (Motor 3)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.42
Minimum Output
Frequency (Fmin)
(Motor 3)
0.10
to 599.00 Hz
1.50
01.43
Minimum Output
Voltage (Vmin)
(Motor 3)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...