E-23
Following is the flow chart for status switch:
Start
Not Ready to Switch On
X0XX0000
Switch On Disable
X1XX0000
Ready to Switch On
X01X0001
Switch On
X01X0011
Operation Enable
X01X0111
0XXXX110
QStop=1
0XXXXX0X
or
0XXXX01X
QStop=0
0XXXX111
0XXXX110
0XXX1111
0XXX0110
0XXX1111
0XXXXX0X
0XXXX01X
or
0XXXXX0X
QStop=0
Quick Stop Active
X00X0111
0XXX1111
QStop=1
0XXXX01X
QStop=0
Fault Reaction Active
X0XX1111
Fault
X0XX1000
0XXXXX0X
or
Font=0
XXXXXXXX
Power
Disable
Fault
Power
Enable
<State switching flowchart>
9.
According to DSP-402
standard for motion control, by using c
ontrol word 0x6040 bit 4
~bit6 to make the drive is running or not, and the definition is as follows: