Chapter 4 Parameters
4-170
13.00= 3
FWD
CCW
13.00= 2
A phas e leads B phase
A phas e
B phas e
PULSE
GE NERATOR
A phas e
B phas e
CW
REV
CW
A phas e
B phas e
B phas e leads A phase
When receiving a forward command, motor will rotate in
countercloc kwise direction (see from output s ide).
When receiving a rev erse command, motor wil l rotate i n
cloc kwise direction (see from output s ide).
When enc oder rotates in cl oc kwise di rection (see from input side).
At this moment, A phase leads B phase.
13.01
PG Pulse Range
Settings
1 to 20000
Factory Setting: 600
A Pulse Generator (PG) is used as a sensor that provides a feedback signal of the motor
speed. This parameter defines the number of pulses for each cycle of the PG control.
This parameter setting is the resolution of encoder. With the higher resolution, the speed
control will be more precise.
13.02
Motor Pole Number (Motor 0)
Unit: 1
Settings
2 to 10
Factory Setting: 4
The pole number should be even (can’t be odd).
13.03
Proportional Gain (P)
Unit: 0.01
Settings
0.0 to 10.0
Factory Setting: 1.0
This parameter is used to set the gain (P) when using PG for the closed-loop speed control.
The proportional gain is mainly used to eliminate the fault. The large proportional gain(P) will
get the faster response to decrease the fault. Too large proportional gain will cause large
overshoot and oscillation and decrease the stable.
This parameter can be used to set the proportional gain (P) to decide the response speed.
With large proportional gain, it will get faster response. Too large proportional gain may cause
system oscillation. With small proportional gain, it will get slower response.
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...