Chapter 4 Parameters
4-53
Output
frequency
F requenc y
command
01.07
Output frequency
upper l imit
01.08
Output frequency
lower limit
01.09
Acceleration Time 1 (Taccel 1)
Unit: second
01.10
Deceleration Time 1 (Tdecel 1)
Unit: second
01.11
Acceleration Time 2 (Taccel 2)
Unit: second
01.12
Deceleration Time 2 (Tdecel 2)
Unit: second
Settings
0.1 to 600.0 sec / 0.01 to 600.0 sec
Factory Setting: 10.0
Acceleration/deceleration time 1 or 2 can be switched by setting the external terminals MI3~
MI12(MI7~MI12 are optional) to 7 (set Pr.04.05~Pr.04.08 to 7 or Pr.11.06~Pr.11.11 to 7). The
factory settings are acceleration time 1.
The Acceleration Time is used to determine the time required for the AC motor drive to ramp
from 0 Hz to Maximum Output Frequency (Pr.01.00). The Deceleration Time is used to
determine the time required for the AC motor drive to decelerate from the Maximum Output
Frequency (Pr.01.00) down to 0 Hz.
If the setting of the acceleration/deceleration time is too short, it may trigger the protection
(Pr.06.01(Over-Current Stall Prevention during Accel) or Pr.06.00(Over-Voltage Stall
Prevention)) and make the actual acceleration/deceleration time be larger than this setting.
If the setting of the acceleration time is too short, it may cause over-current during acceleration
and damage the motor or trigger the protection function.
If the setting of the deceleration time is too short, it may cause over-current during deceleration
or over voltage of the AC motor drive and damage the motor or trigger the protection function.
It can use suitable brake resistor to decelerate the AC motor drive in short time and prevent
internal over voltage. Refer to Appendix B for brake resistor.
When enabling Pr.01.17(Acceleration S-Curve) and Pr.01.18(Deceleration S-Curve), the
actual acceleration/deceleration time will be longer than the setting.
Related parameters: Pr.01.16(Auto acceleration / deceleration (refer to Accel/Decel time
setting)), Pr.01.17(Acceleration S-Curve), Pr.01.18(Deceleration S-Curve), Pr.04.05(Multi-
function Input Terminal (MI3)), Pr.04.06(Multi-function Input Terminal (MI4)), Pr.04.07(Multi-
function Input Terminal (MI5)) and Pr.04.08(Multi-function Input Terminal (MI6))
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...