Chapter 4 Parameters
4-13
Group 4 Input Function Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
04.00
Keypad
Potentiometer Bias
0.0 to 200.0 %
0.0
04.01
Keypad
Potentiometer Bias
Polarity
0: Positive bias
1: Negative bias
0
04.02
Keypad
Potentiometer Gain
0.1 to 200.0 %
100.0
04.03
Keypad
Potentiometer
Negative Bias,
Reverse Motion
Enable/Disable
0: No negative bias command
0
1: Negative bias: REV motion enabled
04.04 2-wire/3-wire
Operation Control
Modes
0: 2-wire: FWD/STOP, REV/STOP
0
1: 2-wire: FWD/REV, RUN/STOP
2: 3-wire operation
04.05 Multi-function
Input
Terminal (MI3)
0: No function
1
1: Multi-Step speed command 1
2: Multi-Step speed command 2
04.06 Multi-function
Input
Terminal (MI4)
3: Multi-Step speed command 3
2
4: Multi-Step speed command 4
5: External reset
04.07 Multi-function
Input
Terminal (MI5)
6: Accel/Decel inhibit
3
7: Accel/Decel time selection command
8: Jog Operation
04.08 Multi-function
Input
Terminal (MI6)
9: External base block
4
10: Up: Increment master frequency
11: Down: Decrement master frequency
12: Counter Trigger Signal
13: Counter reset
14: E.F. External Fault Input
15: PID function disabled
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...