Chapter 4 Parameters
4-164
12.05
Max. AVI3 Scale Percentage
Unit: %
Settings
0.0 to 100.0%
Factory Setting: 100.0
12.06
Min. ACI2 Input Current
Unit: mA
Settings
0.0 to 20.0mA
Factory Setting: 4.0
12.07
Min. ACI2 Scale Percentage
Unit: %
Settings
0.0 to 100.0%
Factory Setting: 0.0
12.08
Max. ACI2 Input Current
Unit: mA
Settings
0.0 to 20.0mA
Factory Setting: 20.0
12.09
Max. ACI2 Scale Percentage
Unit: %
Settings
0.0 to 100.0%
Factory Setting: 100.0
12.10
AI2 Function Selection
Factory Setting: 0
Settings
0
Disabled
1
Source of the 1st frequency
2
Source of the 2nd frequency
3
PID Set Point (PID enable)
4
Positive
PID
feedback
5
Negative
PID
feedback
12.11
AI2 Analog Signal Mode
Factory Setting: 1
Settings
0
ACI3 analog current (0.0 ~ 20.0mA)
1
AVI4 analog voltage (0.0 ~ 10.0V)
Besides parameters settings, the voltage/current mode should be used with the switch.