Chapter 4 Parameters
4-167
Pr.12.22 = [(full scale voltage)/10]*100%.
Example: When using voltmeter with full scale (5V), Pr.12.22 should be set to 5/10*100%=50%. If
Pr.12.21 is set to 0, the output voltage will correspond to the max. output frequency.
12.23
AO2Terminal Analog Signal Mode
Factory Setting: 0
Settings
0
AVO2
1
ACO2 (analog current 0.0 to 20.0mA)
2
ACO2 (analog current 4.0 to 20.0mA)
Besides parameter setting, the voltage/current mode should be used with the switch.
AVI3
ACI2
AVI4
ACI3
AVO1
ACO1
AVO2
ACO2
12.24
AO2 Analog Output Signal
Factory Setting: 0
Settings
0
Analog
Frequency
1
Analog Current (0 to 250% rated current)
12.25
AO2 Analog Output Gain
Unit: %
Settings
1 to 200%
Factory Setting: 100
Setting method for the AO2 is the same as the AO1.
12.26
AUI Analog Input Selection
Factory Setting: 0
Settings
0
No
function
1
Source of the 1st frequency
2
Source of the 2nd frequency
12.27
AUI Analog Input Bias
Unit: %
Settings
0.00 to 200.00%
Factory Setting: 0.00