Chapter 5 Troubleshooting
|
5-4
5.5 Over Heat (OH1)
AC motor drive ov erheats
Heat sink overheats
Chec k if temperature of heat sink
is greater than 90
O
C
No
No
No
Yes
Yes
Yes
Yes
Yes
No
Reduce load
No
Temperature detection malfunctions.
Please c ontact D ELTA.
If cooling fan functions normally
Change cooling f an
Chec k if cooling f an is jammed
Remove
obstruct ion
Chec k if surrounding temperature
is within specification
Adjust surrounding temperature
to specification
Maybe AC motor drive has malfunction or
misoperation due to noise. Please contact
DELTA.
Is load too large
5.6 Overload
OL1/ OL2
OL
Reduce load or increase the power of AC motor drive
Check for correct settings at
Pr. 06-06 and 06-07
Yes
Yes
No
No
Modify setting
Is load too large
Maybe AC motor drive has malfunction
or misoperation due to noise.
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...