E-10
E.1.4.4 EMCY (Emergency Object)
Emergency objects are triggered when hardware failure occurs for a warning
interrupt. The data format of a emergency object is a 8 bytes data as shown in the
following:
Byte 0
1
2
3 4 5 6 7
Content Emergency
Fault
Code
Fault register
(Object 1001H)
Manufacturer specific Fault Field
Definition of Emergency Object:
Display
Controller
Fault
Code
Description
CANopen
Fault
Code
CANopen
Fault
Register
(bit 0~7)
0001H
Over current
2130H 1
0002H
Over voltage
3210H 2
0003H
Overheating
4310H 3
0005H
Overload
2310H 1
0006H
Overload 1
2310H 1
0007H
Overload 2
2310H 1
0008H
External Fault
9000H 5
0009H
Over-current during acceleration
2310H
1
000AH
Over-current during deceleration
2310H
1
000BH
Over-current during constant speed
operation
2310H 1
000CH Ground
fault
2240H
1
000DH
Lower than standard voltage
3220H 2
000EH Phase
Loss
3130H 2
000FH
External Base Block
9000H 5
0011H
Software protection failure
6320H 5
0013H
Internal EEPROM can not be
programmed
5530H 5
0014H
Internal EEPROM can not be read
5530H 5
0015H
CC (current clamp)
5000H 5
0016H
OV hardware fault
5000H 2
0017H
GFF hardware fault
5000H 2
0018H
OC hardware fault
5000H 1
0019H U-phase
fault
2300H 1
001AH V-phase
fault
2300H 1
001BH W-phase
fault
2300H 1
001CH
OV or LV
3210H 2
001DH
Temperature sensor fault
4310H 3
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...