Chapter 4 Parameters
4-43
4.3 Description of Parameter Settings
Group 0: User Parameters
This parameter can be set during operation
00.00
Identity Code of the AC Motor Drive
Settings
Read Only
Factory setting: ##
00.01
Rated Current Display of the AC Motor Drive
Settings
Read Only
Factory setting: #.#
Pr. 00.00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
Pr.00.01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
115V Series
kW 0.2
0.4
0.75
HP 0.25
0.5
1.0
Pr.00.00
0 2 4
Rated Output
Current (A)
1.6 2.5 4.2
Max. Carrier
Frequency
15kHz
230V Series
kW 0.2
0.4
0.75
1.5
2.2 3.7 5.5 7.5 11 15
HP 0.25
0.5
1.0
2.0 3.0 5.0 7.5 10 15 20
Pr.00.00
0 2 4 6 8 10 12 14 16 18
Rated Output
Current (A)
1.6 2.5 4.2 7.5 11.0 17 25 33 45 65
Max. Carrier
Frequency
15kHz
460V Series
kW 0.4
0.75
1.5
2.2
3.7 5.5 7.5 11 15 18.5 22
HP
0.5 1.0 2.0 3.0 5.0 7.5 10 15 20 25 30
Pr.00.00 3 5 7 9 11 13 15 17 19 21 23
Rated Output
Current (A)
1.5 2.5 4.2 5.5 8.5 13 18 24 32 38 45
Max. Carrier
Frequency
15kHz
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...