Chapter 4 Parameters
4-4
Group 1 Basic Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
01.00
Maximum Output
Frequency (Fmax)
50.00 to 599.00 Hz
60.00
01.01
Maximum Voltage
Frequency (Fbase)
(Motor 0)
0.10 to 599.00 Hz
60.00
01.02
Maximum Output
Voltage (Vmax)
(Motor 0)
115V/230V series: 0.1V to 255.0V
220.0
460V series: 0.1V to 510.0V
440.0
01.03
Mid-Point Frequency
(Fmid) (Motor 0)
0.10 to 599.00 Hz
1.50
01.04
Mid-Point Voltage
(Vmid) (Motor 0)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.05
Minimum Output
Frequency (Fmin)
(Motor 0)
0.10 to 599.00 Hz
1.50
01.06
Minimum Output
Voltage (Vmin)
(Motor 0)
115V/230V series: 0.1V to 255.0V
10.0
460V series: 0.1V to 510.0V
20.0
01.07
Output Frequency
Upper Limit
0.1 to 120.0%
110.0
01.08
Output Frequency
Lower Limit
0.0 to100.0 %
0.0
01.09
Accel Time 1
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.10
Decel Time 1
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.11
Accel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.12
Decel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
10.0
01.13 Jog
Acceleration
Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
01.14 Jog
Deceleration
Time
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
01.15
Jog Frequency
0.10 Hz to 599.00 Hz
6.00
01.16
Auto acceleration /
0: Linear Accel/Decel
0
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...