Chapter 4 Parameters
4-90
01.00=60.00 Hz
AVI
ACI
analog input
04.14=70
04.18=50
04.12=30
04.16=0
04.11=0V 04.15=4mA
04.13=10V
04.17=20mA
04.04
Multi-function Input Terminal (MI1, MI2) 2-wire/ 3-wire Operation Control Modes
Factory Setting: 0
Settings
0
2-wire: FWD/STOP, REV/STOP
1 2-wire:
FWD/REV,
RUN/STOP
2 3-wire
Operation
There are three different types of control modes:
04.04
External Terminal
0
2-wire
FWD /STOP
REV / STOP
VFD-E
MI1:("OPEN":STOP)
("CLOSE":FWD)
MI2:("OPEN": STOP)
("CLOSE": REV)
DCM
FWD/STOP
REV/STOP
1
2-wire
FWD/ REV
RUN / STOP
VFD-E
MI1:("OPEN":STOP)
("CLOSE":RUN)
MI2:("OPEN": FWD)
("CLOSE": REV)
DCM
RUN/STOP
FWD/REV