Chapter 4 Parameters
4-171
13.04
Integral Gain ( I )
Unit: 0.01
Settings
0.00 to 100.00 sec
Factory Setting: 1.00
0.00
Disable
The integral controller is used to eliminate the fault during stable system. The integral control
doesn’t stop working until fault is 0. The integral is acted by the integral time. The smaller
integral time is set, the stronger integral action will be. It is helpful to reduce overshoot and
oscillation to make a stable system. At this moment, the decreasing fault will be slow. The
integral control is often used with other two controls to become PI controller or PID controller.
This parameter is used to set the integral time of I controller. When the integral time is long, it
will have small gain of I controller, the slower response and bad external control. When the
integral time is short, it will have large gain of I controller, the faster response and rapid
external control.
When the integral time is too small, it may cause system oscillation.
When it is set to 0.0, the integral function is disabled.
13.05
Speed Control Output Frequency Limit
Unit: Hz
Settings
0.00 to 100.00Hz
Factory Setting: 10.00
This parameter is used to limit the max. output frequency.
From the following PG speed diagram, output frequency (H) = frequency command (F) +
speed detection value via PG feedback. With the speed change of motor load, the speed
change will be sent to drive via PG card to change the output frequency. So this parameter
can be used to decrease the speed change of motor load.
13.06
Speed Feedback Display Filter
Unit: 2ms
Settings
0 to 9999 (*2ms)
Factory Setting: 500
When Pr.0.04 is set to 14, its display will be updated regularly. This update time is set by
Pr.13.06.
With the large setting in Pr.13.06, it can slow the response speed to prevent the blinking of
digital number on the digital keypad. Too large setting may cause the delay of RPM value via
PG card.
Related parameter: Pr.00.04(Content of Multi-function Display)
13.09
Speed Feedback Filter
Unit: 2ms
Settings
0 to 9999 (*2ms)
Factory Setting: 16
This parameter is the filter time from the speed feedback to the PG card. Too large setting may
cause slow feedback response.
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...