D-38
D.4.10 Communication Addresses for Devices (only for PLC2 mode)
Device
Range
Type
Address (Hex)
X 00–17
(octal)
Bit
0400-040F
Y 00–17
(octal)
Bit
0500-050F
T 00-15 Bit/word 0600-060F
M 000-159
Bit
0800-089F
M 1000-1031
Bit
0BE8-0C07
C 0-7 Bit/word 0E00-0E07
D 00-29 Word
1000-101D
D 1000-1044 Word
13E8-1414
D.4.11 Function Code (only for PLC2 mode)
Function Code
Description
Supported Devices
H1
Read coil status
Y, M, T, C
H2
Read input status
X, Y, M, T, C
H3
Read one data
T, C, D
H5
Force changing one coil status
Y, M, T, C
H6
Write in one data
T, C, D
HF
Force changing multiple coil status
Y, M, T, C
H10
Write in multiple data
T, C, D
NOTE:
In PLC1 mode, the Modbus communication will correspond to the registers of motor drive.
In PLC2 mode, the Modbus communication will correspond to the registers of internal PLC.
For example:
In PLC1 mode, communication register 0400H corresponds to parameter 04.00.
In PLC2 mode, communication register 0400H corresponds to X0.