UL Compliance
380–480V, frame sizes D, E and F
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or 500 V,
or 600 V depending on the drive voltage rating. With the proper fusing, the drive Short Circuit Current Rating (SCCR) is
100,000 Arms.
Size/
Type
Bussmann
E1958
JFHR2**
Bussmann
E4273
T/JDDZ**
SIBA
E180276
JFHR2
LittelFuse
E71611
JFHR2**
Ferraz-
Shawmut
E60314
JFHR2**
Bussmann
E4274
H/JDDZ**
Bussmann
E125085
JFHR2*
Internal
Option
Bussmann
P110
FWH-
300
JJS-
300
2061032.315
L50S-300
A50-P300
NOS-
300
170M3017
170M3018
P132
FWH-
350
JJS-
350
2061032.35
L50S-350
A50-P350
NOS-
350
170M3018
170M3018
P160
FWH-
400
JJS-
400
2061032.40
L50S-400
A50-P400
NOS-
400
170M4012
170M4016
P200
FWH-
500
JJS-
500
2061032.50
L50S-500
A50-P500
NOS-
500
170M4014
170M4016
P250
FWH-
600
JJS-
600
2062032.63
L50S-600
A50-P600
NOS-
600
170M4016
170M4016
Table 5.14 Frame Size D, Line Fuses, 380–480V
Size/
Type
Bussma
nn PN*
Rating
Ferraz
Siba
P315
170M4
017
700A,
700V
6.9URD31D08A0
700
20 610 32.700
P355
170M6
013
900A,
700V
6.9URD33D08A0
900
20 630 32.900
P400
170M6
013
900A,
700V
6.9URD33D08A0
900
20 630 32.900
P450
170M6
013
900A,
700V
6.9URD33D08A0
900
20 630 32.900
Table 5.15 Frame Size E, Line Fuses, 380–480V
Size/
Type
Bussmann
PN*
Rating
Siba
Internal
Bussmann
Option
P500
170M7081
1600A,
700V
20 695 32.1600
170M7082
P560
170M7081
1600A,
700V
20 695 32.1600
170M7082
P630
170M7082
2000A,
700V
20 695 32.2000
170M7082
P710
170M7082
2000A,
700V
20 695 32.2000
170M7082
P800
170M7083
2500A,
700V
20 695 32.2500
170M7083
P1M0
170M7083
2500A,
700V
20 695 32.2500
170M7083
Table 5.16 Frame Size F, Line Fuses, 380–480V
Size/Type
Bussmann
PN*
Rating
Siba
P500
170M8611
1100A,
1000V
20 781 32.1000
P560
170M8611
1100A,
1000V
20 781 32.1000
P630
170M6467
1400A,
700V
20 681 32.1400
P710
170M6467
1400A,
700V
20 681 32.1400
P800
170M8611
1100A,
1000V
20 781 32.1000
P1M0
170M6467
1400A,
700V
20 681 32.1400
Table 5.17 Frame Size F, Inverter Module DC Link Fuses, 380–480V
*170M fuses from Bussmann shown use the -/80 visual indicator, -
TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size
and amperage may be substituted for external use
**Any minimum 500V UL-listed fuse with associated current rating
may be used to meet UL requirements.
How to Install
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
5-19
5
5
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...