6.1.13 Cascade Controller Wiring Diagram
The wiring diagram shows an example with the built-in BASIC Cascade Controller with one variable-speed pump (lead) and
two fixed-speed pumps, a 4-20 mA transmitter and system safety interlock.
Figure 6.11
6.1.14 Start/Stop Conditions
Commands assigned to digital inputs. See
Digital Inputs
, parameter group 5-1*.
Variable-speed pump (lead)
Fixed-speed pumps
Start (SYSTEM START /STOP)
Ramps up (if stopped and there is a
demand)
Staging (if stopped and there is a demand)
Lead Pump Start
Ramps up if SYSTEM START is active
Not affected
Coast (EMERGENCY STOP)
Coast to stop
Cut out (built in relays are de-energized)
External Interlock
Coast to stop
Cut out (built in relays are de-energized)
Table 6.1