Line
Power
Supply
3
x
380–480V
AC
-
Normal
overload
110%
for
1
minute
Adjustable
Frequency
Drive
Typical
Shaft
Output
[kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P4K0
4
P5K5
5.5
P7K5
7.5
Typical
Shaft
Output
[hp]
at
460V
1.5
2.0
2.9
4.0
5.0
7.5
10
IP20/Chassis
(A2+A3
may
be
converted
to
IP21
using
a
conversion
kit.
(Please
see
also
items
Mechanical
mounting
in
the
Instruction
Manual
and
IP
1/Type
1
Enclosure
kit
in
the
Design
Guide.))
A2
A2
A2
A2
A2
A3
A3
IP55/NEMA
12
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
IP66/NEMA
12
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output
current
130BA058.10
Continuous
(3
x
380–440V)
[A]
3
4.1
5.6
7.2
10
13
16
Intermittent
(3
x
380–440V)
[A]
3.3
4.5
6.2
7.9
11
14.3
17.6
Continuous
(3
x
441–480
V)
[A]
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent
(3
x
441–480
V)
[A]
3.0
3.7
5.3
6.9
9.0
12.1
15.4
Continuous
kVA
(400V
AC)
[kVA]
2.1
2.8
3.9
5.0
6.9
9.0
11.0
Continuous
kVA
(460V
AC)
[kVA]
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Max.
cable
size:
(line
power,
motor,
brake)
[[mm
2
/
AWG]
2)
4/10
Max.
input
current
130BA057.10
Continuous
(3
x
380–440
V)
[A]
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent
(3
x
380–440
V)
[A]
3.0
4.1
5.5
7.2
9.9
12.9
15.8
Continuous
(3
x
441–480
V)
[A]
2.7
3.1
4.3
5.7
7.4
9.9
13.0
Intermittent
(3
x
441–480
V)
[A]
3.0
3.4
4.7
6.3
8.1
10.9
14.3
Max.
pre-fuses
1)
[A]
10
10
20
20
20
32
32
Environment
Estimated
power
loss
at
rated
max.
load
[W]
4)
58
62
88
116
124
187
255
Weight
enclosure
IP20
(lb
[kg])
10.6
[4.8]
10.8
[4.9]
10.8
[4.9]
10.8
[4.9]
10.8
[4.9]
14.6
[6.6]
14.6
[6.6]
Weight
enclosure
IP21
(lb
[kg])
Weight
enclosure
IP55
(lb
[kg])
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
31.3
[14.2]
31.3
[14.2]
Weight
enclosure
IP66
(lb
[kg])
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
21.4/29.8
[9.7/13.5]
31.3
[14.2]
31.3
[14.2]
Efficiency
3)
0.96
0.97
0.97
0.97
0.97
0.97
0.97
Table
8.3
Line
Power
Supply
3
x
380–480V
AC
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-3
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...