Line Power Supply 3 x 380–480 VAC
P315
P355
P400
P450
Typical Shaft output at 400 V [kW]
315
355
400
450
Typical Shaft output at 460 V [HP]
450
500
600
600
Enclosure IP21
E1
E1
E1
E1
EnclosureIP54
E1
E1
E1
E1
Enclosure IP00
E2
E2
E2
E2
Output current
130BA230.10
Continuous
(at 400 V) [A]
600
658
745
800
Intermittent (60 sec overload)
(at 400 V) [A]
660
724
820
880
Continuous
(at 460/ 480 V) [A]
540
590
678
730
Intermittent (60 sec overload)
(at 460/480 V) [A]
594
649
746
803
Continuous KVA
(at 400 V) [KVA]
416
456
516
554
Continuous KVA
(at 460 V) [KVA]
430
470
540
582
Max. input current
130BA229.10
Continuous
(at 400 V) [A]
590
647
733
787
Continuous
(at 460/ 480 V) [A]
531
580
667
718
Max. cable size, line power, motor
and load share [mm
2
(AWG
2)
)]
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
4x240
(4x500 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses [A]
1
700
900
900
900
Estimated power loss
at rated max. load [W, hp]
4)
, 400 V
6790, 9.11
7701, 10.33
8879, 11.91
9670, 12.97
Estimated power loss
at rated max. load [W, hp]
4)
, 460 V
6082, 8.16
6953, 9.32
8089, 10.85
8803, 11.81
Weight,
enclosure IP21, IP 54 (lb [kg])
579.8 [263]
595.3 [270]
599.7 [272]
690 [313]
Weight,
enclosure IP00 (lb [kg])
487.2 [221]
515.9 [234]
520.3 [236]
610.7 [277]
Efficiency
4)
0.98
Output frequency
0–600 Hz
Heatsink overtemp. trip
230°F [110
°
C]
Power card ambient trip
154°F [68
°
C]
Table 8.8
General Specifications and ...
VLT
®
HVAC Drive Design Guide
8-8
MG11BB22 - VLT
®
is a registered Danfoss trademark
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...