7.3 Network Configuration
7.3.1 Adjustable Frequency Drive Set-up
Set the following parameters to enable the FC protocol for
the Adjustable frequency drive.
Parameter Number Setting
8-30 Protocol
FC
8-31 Address
1–126
8-32 Baud Rate
2400–115200
8-33 Parity / Stop
Bits
Even parity, 1 stop bit (default)
Table 7.3
7.4 FC Protocol Message Framing Structure
7.4.1 Content of a Character (byte)
Each character transferred begins with a start bit. Then 8
data bits are transferred, corresponding to a byte. Each
character is secured via a parity bit. This bit is set at "1"
when it reaches parity. Parity is when there is an equal
number of 1s in the 8 data bits and the parity bit in total.
A stop bit completes a character, thus consisting of 11 bits
in all.
Figure 7.5
7.4.2 Message Structure
Each message has the following structure:
1.
Start character (STX)=02 Hex
2.
A byte denoting the message length (LGE)
3.
A byte denoting the Adjustable frequency drive
address (ADR)
A number of data bytes (variable, depending on the type
of message) follows.
A data control byte (BCC) completes the message.
STX
LGE
ADR
DATA
BCC
195NA099.10
Figure 7.6
RS-485 Installation and Set...
VLT
®
HVAC Drive Design Guide
7-4
MG11BB22 - VLT
®
is a registered Danfoss trademark
7
7
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...