General Purpose I/O
SW. ver. XX.XX
MCB 101
FC Series
Code No. 130BXXXX
B slot
X30/
AIN4
7
8
6
5
4
3
2
1
9
10
11
12
AIN3
GND(2)
24V
AOUT2
DOUT4
DOUT3
GND(1)
DIN7
CO
M
DIN
DIN8
DIN9
130BA208.10
Figure 3.3
Galvanic isolation in the MCB 101
Digital/analog inputs are galvanically isolated from other
inputs/outputs on the MCB 101 and in the control card of
the Adjustable frequency drive. Digital/analog outputs in
the MCB 101 are galvanically isolated from other inputs/
outputs on the MCB 101, but not from those on the
control card of the Adjustable frequency drive.
If the digital inputs 7, 8 or 9 are to be switched by use of
the internal 24V power supply (terminal 9) the connection
between terminal 1 and 5 which is shown in
Figure 3.4
has
to be established.
130BA209.10
1
2
3
4
5
6
7
8
9
10
11 12
COM DIN
DIN7
DIN8
DIN9
GND(1)
DOUT3
0/24VDC
DOUT4 0/24VDC
AOUT2 0/4-20mA 24V
GND(2)
AIN3
AIN4
RIN=
5kohm
RIN=
10kohm
0-10
VDC
0-10
VDC
0V
24V
0V
24V
24V DC
0V
0V
24V DC
<500 ohm
>600 ohm
>600 ohm
X30/
DIG IN
DIG &
ANALOG
OUT
ANALOG
IN
CPU
CAN BUS
CPU
Control card (FC 100/200/300)
General Purpose
I/O option MCB 101
PLC
(PNP)
PLC
(NPN)
Figure 3.4 Principle Diagram
3.1.3 Digital Inputs - Terminal X30/1-4
Parameters for set-up: 5-16, 5-17 and 5-18
Numb
er of
digital
inputs
Volta
ge
level
Voltage levels
Tolerance
Max. Input
impedance
3
0–24
V DC
PNP type:
Common = 0V
Logic “0”: Input <
5V DC
Logic “0”: Input >
10V DC
NPN type:
Common = 24V
Logic “0”: Input >
19V DC
Logic “0”: Input <
14V DC
± 28V
continuous
± 37V in
minimum
10 sec.
Approx. 5kΩ
Table 3.1
3.1.4 Analog Voltage Inputs - Terminal
X30/10-12
Parameters for set-up: 6-3*, 6-4* and 16-76
Number of
analog voltage
inputs
Standardized
input signal
Tolerance Reso
lutio
n
Max. Input
impedance
2
0–10V DC
± 20V
contin-
uously
10
bits
Approx. 5K
Ω
Table 3.2
3.1.5 Digital Outputs - Terminal X30/5-7
Parameters for set-up: 5-32 and 5-33
Number of digital
outputs
Output level
Tolerance Max.impedan
ce
2
0 or 2 V DC
± 4V
≥ 600
Ω
Table 3.3
3.1.6 Analog Outputs - Terminal X30/5+8
Parameters for set-up: 6-6* and 16-77
Number of analog
outputs
Output signal
level
Tolerance
Max.imp
edance
1
0/4–20mA
± 0.1mA
< 500
Ω
Table 3.4
VLT
®
HVAC Drive Selection
VLT
®
HVAC Drive Design Guide
3-2
MG11BB22 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...