stopped in order to prevent overheating. If the motor is
overloaded without reaching the temperature where the
ETR shuts off the motor, the torque limit protects the
motor and application for becoming overloaded.
ETR is activated in
1-90 Motor Thermal Protection
and is
controlled in
4-16 Torque Limit Motor Mode
. The time
before the torque limit warning trips the Adjustable
frequency drive is set in
14-25 Trip Delay at Torque Limit
.
Introduction to VLT® HVAC D...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
2-45
2
2