Control card, RS-485 serial communication
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs
2
Terminal number
27, 29
1)
Voltage level at digital/frequency output
0–24V
Max. output current (sink or source)
40mA
Max. load at frequency output
1 k
Ω
Max. capacitive load at frequency output
10nF
Minimum output frequency at frequency output
0Hz
Maximum output frequency at frequency output
32kHz
Accuracy of frequency output
Max. error: 0.1% of full scale
Resolution of frequency outputs
12 bit
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number
12, 13
Max. load
200mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
2
Relay 01 Terminal number
1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
240V AC, 2A
Max. terminal load (AC-15)
1)
(Inductive load
@
cos
φ
0.4)
240V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
60V DC, 1A
Max. terminal load (DC-13)
1)
(Inductive load)
24V DC, 0.1A
Relay 02 Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
2)3)
400V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load
@
cos
φ
0.4)
240V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load)
80V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load)
24V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load)
240V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load
@
cos
φ
0.4)
240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load)
50V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load)
24V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
24V DC 10mA, 24V AC 20mA
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300V AC 2A
Control card, 10 V DC output
Terminal number
50
Output voltage
10.5V
±
0.5V
Max. load
25mA
The 10V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-19
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...