8.2 General Specifications
Line power supply (L1, L2, L3)
Supply voltage
200–240 V
±
10%, 380–480 V
±
10%, 525–690 V
±
10%
AC line voltage low / line drop-out:
During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage
drops below the minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated
supply voltage. Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency
drive's lowest rated supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. imbalance temporary between line phases
3.0% of rated supply voltage
True Power Factor ()
≥
0.9 nominal at rated load
Displacement Power Factor (cos) near unity
(> 0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
enclosure type A
maximum twice/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
enclosure type B, C
maximum once/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
enclosure type D, E, F
maximum once/2 min.
Environment according to EN60664-1
overvoltage category III / pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–1000Hz
*
Switching on output
Unlimited
Ramp times
1–3600 sec.
*
Dependent on power size.
Torque characteristics
Starting torque (Constant torque)
maximum 110% for 1 min.
*
Starting torque
maximum 135% up to 0.5 sec.
*
Overload torque (Constant torque)
maximum 110% for 1 min.
*
*Percentage relates to the adjustable frequency drive's nominal torque.
Cable lengths and cross-sections
Max. motor cable length, shielded/armored
VLT
®
HVAC Drive: 492 ft [150 m]
Max. motor cable length, non-shielded/unarmored
VLT
®
HVAC Drive: 984 ft [300 m]
Max. cross-section to motor, line power, load sharing and brake *
Maximum cross-section to control terminals, rigid wire
0.0023 in
2
[1.5 mm
2
]/16 AWG (2 x 0.0012 in
2
[0.75 mm
2
])
Maximum cross-section to control terminals, flexible cable
0.00016 in
2
[1 mm
2
]/18 AWG
Maximum cross-section to control terminals, cable with enclosed core
0.0008 in
2
[0.5 mm
2
]/20 AWG
Minimum cross-section to control terminals
0.00039 in
2
[0.25 mm
2
]
* See Line Power Supply tables for more information!
Digital inputs
Programmable digital inputs
4 (6)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33,
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic'0' PNP
< 5 V DC
Voltage level, logic'1' PNP
> 10 V DC
Voltage level, logic '0' NPN
> 19 V DC
Voltage level, logic '1' NPN
< 14 V DC
Maximum voltage on input
28 V DC
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-17
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...