Line Power Supply 3 x 525–690V AC
P710
P800
P900
P1M0
P1M2
P1M4
Typical Shaft output at 550V
[kW]
560
670
750
850
1000
1100
Typical Shaft output at 575V
[HP]
750
950
1050
1150
1350
1550
Typical Shaft output at 690V
[kW]
710
800
900
1000
1200
1400
Enclosure IP21, 54 without/
with options cabinet
F1/ F3
F1/ F3
F1/ F3
F2/F4
F2/ F4
F2/F4
Output current
130BA230.10
Continuous
(at 550V) [A]
763
889
988
1108
1317
1479
Intermittent (60 s overload, at
550V) [A]
839
978
1087
1219
1449
1627
Continuous
(at 575/690V) [A]
730
850
945
1060
1260
1415
Intermittent (60 s overload, at
575/690V) [A]
803
935
1040
1166
1386
1557
Continuous KVA
(at 550V) [KVA]
727
847
941
1056
1255
1409
Continuous KVA
(at 575V) [KVA]
727
847
941
1056
1255
1409
Continuous KVA
(at 690V) [KVA]
872
1016
1129
1267
1506
1691
Table 8.14
General Specifications and ...
VLT
®
HVAC Drive Design Guide
8-14
MG11BB22 - VLT
®
is a registered Danfoss trademark
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...