followed by the high-order byte. The CRC high-order byte
is the last byte sent in the message.
7.8.8 Coil Register Addressing
In Modbus, all data are organized in coils and holding
registers. Coils hold a single bit, whereas holding registers
hold a 2-byte word (i.e., 16 bits). All data addresses in
Modbus messages are referenced to zero. The first
occurrence of a data item is addressed as item number
zero. For example: The coil known as ‘coil 1’ in a
programmable controller is addressed as coil 0000 in the
data address field of a Modbus message. Coil 127 decimal
is addressed as coil 007EHEX (126 decimal).
Holding register 40001 is addressed as register 0000 in the
data address field of the message. The function code field
already specifies a ‘holding register’ operation. Therefore,
the ‘4XXXX’ reference is implicit. Holding register 40108 is
addressed as register 006BHEX (107 decimal).
Coil Number
Description
Signal Direction
1-16
Adjustable frequency drive control word (see table below)
Master to slave
17-32
Adjustable frequency drive speed or setpoint reference Range 0x0 – 0xFFFF
(-200% ... ~200%)
Master to slave
33-48
Adjustable frequency drive status word (see table below)
Slave to master
49-64
Open-loop mode: Adjustable frequency drive output frequency Closed-loop
mode: Adjustable frequency drive feedback signal
Slave to master
65
Parameter write control (master to slave)
Master to slave
0 =
Parameter changes are written to the RAM of the Adjustable
frequency drive
1 =
Parameter changes are written to the RAM and EEPROM of the
Adjustable frequency drive.
66-65536
Reserved
Table 7.14
Coil
0
1
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
No DC brake
04
Coast stop
No coast stop
05
Quick stop
No quick stop
06
Freeze freq.
No freeze freq.
07
Ramp stop
Start
08
No reset
Reset
09
No jog
Jog
10
Ramp 1
Ramp 2
11
Data not valid
Data valid
12
Relay 1 off
Relay 1 on
13
Relay 2 off
Relay 2 on
14
Set up LSB
15
Set up MSB
16
No reversing
Reversing
Adjustable frequency drive control word (FC profile)
Table 7.15
Coil
0
1
33
Control not ready
Control ready
34
Adjustable frequency drive
not ready
Adjustable frequency drive
ready
35
Coasting stop
Safety closed
36
No alarm
Alarm
37
Not used
Not used
38
Not used
Not used
39
Not used
Not used
40
No warning
Warning
41
Not at reference
At reference
42
Hand mode
Auto mode
43
Out of freq. range
In frequency range
44
Stopped
Running
45
Not used
Not used
46
No voltage warning
Voltage warning
47
Not in current limit
Current limit
48
No thermal warning
Thermal warning
Adjustable frequency drive status word (FC profile)
Table 7.16
RS-485 Installation and Set...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
7-13
7
7
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...