90
90
06
311
130BA216.10
35 36
Figure 3.9 Connection to 24V Backup Supplier (A5-C2).
3.1.9 Analog I/O option MCB 109
The Analog I/O card is supposed to be used, e.g., in the
following cases:
•
Providing battery backup of clock function on
control card
•
As general extension of analog I/O selection
available on control card, e.g., for multi-zone
control with three pressure transmitters
•
Turning Adjustable frequency drive into de-
central I/O block supporting Building
Management System with inputs for sensors and
outputs for operating dampers and valve servos.
•
Support extended PID controllers with I/Os for
setpoint inputs, transmitter/sensor inputs and
outputs for servos.
Figure 3.10 Principle diagram for Analog I/O mounted in
Adjustable frequency drive.
Analog I/O configuration
3 x analog inputs, capable of handling following:
•
0–10V DC
OR
•
0–20mA (voltage input 0–10V) by mounting a
510
Ω
resistor across terminals (see NB!)
•
4–20mA (voltage input 2–10V) by mounting a
510
Ω
resistor across terminals (see NB)
•
Ni1000 temperature sensor of 1000
Ω
at 32°F
[0
°
C]. Specifications according to DIN43760
•
Pt1000 temperature sensor of 1000
Ω
at 32°F
[0
°
C]. Specifications according to IEC 60751
3 x analog outputs supplying 0–10V DC.
VLT
®
HVAC Drive Selection
VLT
®
HVAC Drive Design Guide
3-6
MG11BB22 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...