Line Power Supply 3 x 525–690V AC
P710
P800
P900
P1M0
P1M2
P1M4
Max. input current
130BA229.10
Continuous
(at 550V) [A]
743
866
962
1079
1282
1440
Continuous
(at 575V) [A]
711
828
920
1032
1227
1378
Continuous
(at 690V) [A]
711
828
920
1032
1227
1378
Max. cable size,motor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size, line power
F1/F2 [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size, line power
F3/F4 [mm
2
(AWG
2)
)]
8x456
8x900 mcm
Max. cable size, loadsharing
[mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-fuses [A]
1)
1600
2000
2500
Est. power loss
at rated max. load [W, hp]
4)
,
600V, F1 & F2
10771, 14.44 12272, 16.46 13835, 18.55 15592, 20.91 18281, 24.52 20825, 27.93
Est. power loss
at rated max. load [W, hp]
4)
,
690V, F1 & F2
11315, 15.17 12903, 17.30 14533, 19.49 16375, 21.96 19207, 25.76 21857, 29.31
Max. added losses of Circuit
Breaker or Disconnect &
Contactor, F3 & F4
427, 0.57
532, 0.71
615, 0.82
665, 0.89
863, 1.16
1044, 1.40
Max Panel Options Losses
400, 0.54
Weight,enclosure IP21, IP54 (lb
[kg])
2213 / 2863
[1004 /
1299]
2213 / 2863
[1004 / 1299]
2213 / 2863
[1004 / 1299]
2747 / 3397
[1246 /
1541]
2747 / 3397
[1246 /
1541]
2822 / 3472
[1280 /
1575]
Weight, Rectifier
Module (lb [kg])
224.9 [102]
224.9 [102]
224.9 [102]
299.8 [136]
299.8 [136]
299.8 [136]
Weight, Inverter
Module (lb [kg])
224.9 [102]
224.9 [102]
299.8 [136]
224.9 [102]
224.9 [102]
299.8 [136]
Efficiency
4)
0.98
Output frequency
0–500Hz
Heatsink overtemp. trip
203°F [95
°
C]
Power card amb. trip
154.4°F [68
°
C]
Table 8.15
1) For type of fuse, see
5.2.8 Fuses
2) American Wire Gauge.
3) Measured using 16.4 ft [5 m] shielded motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerance relates to
variety in voltage and cable conditions). Values are based on a typical motor efficiency (eff2/eff3 border line).
Motors with lower efficiency will also add to the power loss in the Adjustable frequency drive and opposite. If the
switching frequency is increased comed to the default setting, the power losses may rise significantly. LCP and
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-15
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...