Adjustable Frequency Drive, P7K5, T2
Cable
length (ft [m])
AC line
voltage [V]
Rise time
[
μ
sec]
011893-0001
dU/dt
[kV/
μ
sec]
16.4 [5]
230
0.13
0.510
3.090
164 [50]
230
0.23
0.590
2.034
328 [100]
230
0.54
0.580
0.865
492.1 [150]
230
0.66
0.560
0.674
Table 8.18
Adjustable Frequency Drive, P11K, T2
Cable
length (ft [m])
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
118.1 [36]
240
0.264
0.624
1.894
446.2 [136]
240
0.536
0.596
0.896
492.1 [150]
240
0.568
0.568
0.806
Table 8.19
Adjustable Frequency Drive, P15K, T2
Cable
length (ft [m])
AC line
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
98.4 [30]
240
0.556
0.650
0.935
328 [100]
240
0.592
0.594
0.807
492.1 [150]
240
0.708
0.575
0.669
Table 8.20
Adjustable Frequency Drive, P18K, T2
Cable
length (ft [m])
AC line
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
118.1 [36]
240
0.244
0.608
1.993
446.2 [136]
240
0.568
0.580
0.832
492.1 [150]
240
0.720
0.574
0.661
Table 8.21
Adjustable Frequency Drive, P22K, T2
Cable
length (ft [m])
AC line
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
118.1 [36]
240
0.244
0.608
1.993
446.2 [136]
240
0.560
0.580
0.832
492.1 [150]
240
0.720
0.574
0.661
Table 8.22
Adjustable Frequency Drive, P30K, T2
Cable
length (ft [m])
AC line
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
49.2 [15]
240
0.194
0.626
2.581
164 [50]
240
0.252
0.574
1.929
492.1 [150]
240
0.444
0.538
0.977
Table 8.23
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-23
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...