Line Power Supply 3 x 380–480 VAC
P500
P560
P630
P710
P800
P1M0
Typical Shaft output at 400 V
[kW]
500
560
630
710
800
1000
Typical Shaft output at 460 V
[HP]
650
750
900
1000
1200
1350
Enclosure IP21, 54 without/
with options cabinet
F1/F3
F1/F3
F1/F3
F1/F3
F2/F4
F2/F4
Output current
130BA230.10
Continuous
(at 400 V) [A]
880
990
1120
1260
1460
1720
Intermittent (60 sec overload)
(at 400 V) [A]
968
1089
1232
1386
1606
1892
Continuous
(at 460/ 480 V) [A]
780
890
1050
1160
1380
1530
Intermittent (60 sec overload)
(at 460/480 V) [A]
858
979
1155
1276
1518
1683
Continuous KVA
(at 400 V) [KVA]
610
686
776
873
1012
1192
Continuous KVA
(at 460 V) [KVA]
621
709
837
924
1100
1219
Max. input current
130BA229.10
Continuous
(at 400 V) [A]
857
964
1090
1227
1422
1675
Continuous (at 460/480 V) [A]
759
867
1022
1129
1344
1490
Max. cable size,motor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size, line power
F1/F2 [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size, line power
F3/F4 [mm
2
(AWG
2)
)]
8x456
(8x900 mcm)
Max. cable size, loadsharing
[mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-fuses [A]
1
1600
2000
2500
Est. power loss at rated max.
load [W,hp]
4)
, 400 V, F1 & F2
10647, 14.28
12338, 16.55 13201, 17.70 15436, 20.70 18084, 24.25 20358, 27.30
Est. power loss at rated max.
load [W, hp]
4)
, 460 V, F1 & F2
9414, 12.62
11006, 14.76 12353, 16.57 14041, 18.83 17137, 22.98 17752, 23.81
Max. added losses of A1 RFI,
Circuit Breaker or Disconnect,
& Contactor, F3 & F4
963, 1.29
1054, 1.41
1093, 1.47
1230, 1.65
2280, 3.06
2541, 3.41
Max Panel Options Losses
400, 0.54
Weight,
enclosure IP21, IP54 (lb [kg])
2213 [1004]/
2863 [1299]
2213 [1004]/
2863 [1299]
2213 [1004]/
2863 [1299]
2213 [1004]/
2863 [1299]
2747[1246]/
3397[1541]
2747[1246]/
3397[1541]
Weight Rectifier
Module (lb [kg])
224.9 [102]
224.9 [102]
224.9 [102]
224.9 [102]
299.8 [136]
299.8 [136]
Weight Inverter
Module (lb [kg])
224.9 [102]
224.9 [102]
224.9 [102]
299.8 [136]
224.9 [102]
224.9 [102]
Efficiency
4)
0.98
Output frequency
0–600 Hz
Heatsink overtemp. trip
203°F [95
°
C]
Power card ambient trip
154°F [68
°
C]
Table 8.9
General Specifications and ...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
8-9
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...