5.2.9 Non-UL Compliance Fuses
Non-UL Compliance fuses
Adjustable frequency drive
Max. fuse size
Voltage (V)
Type
200–240 V - T2
1K1-1K5
16A
1
200–240
type gG
2K2
25A
1
200–240
type gG
3K0
25A
1
200–240
type gG
3K7
35A
1
200–240
type gG
5K5
50A
1
200–240
type gG
7K5
63A
1
200–240
type gG
11K
63A
1
200–240
type gG
15K
80A
1
200–240
type gG
18K5
125A
1
200–240
type gG
22K
125A
1
200–240
type gG
30K
160A
1
200–240
type gG
37K
200A
1
200–240
type aR
45K
250A
1
200–240
type aR
380–480 V - T4
1K1-1K5
10A
1
380–500
type gG
2K2-3K0
16A
1
380–500
type gG
4K0-5K5
25A
1
380–500
type gG
7K5
35A
1
380–500
type gG
11K–15K
63A
1
380–500
type gG
18K
63A
1
380–500
type gG
22K
63A
1
380–500
type gG
30K
80A
1
380–500
type gG
37K
100A
1
380–500
type gG
45K
125A
1
380–500
type gG
55K
160A
1
380–500
type gG
75K
250A
1
380–500
type aR
90K
250A
1
380–500
type aR
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Table 5.10 Non-UL Fuses 200V to 480V
If UL/cUL is not to be complied with, Danfoss recommends using the following fuses, which will ensure compliance with
EN50178:
Adjustable Frequency Drive
Voltage (V)
Type
P110 - P250
380–480
type gG
P315 - P450
380–480
type gR
Table 5.11 Compliance with EN50178
How to Install
VLT
®
HVAC Drive Design Guide
5-16
MG11BB22 - VLT
®
is a registered Danfoss trademark
5
5
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...