Line
power
supply
3
x
525–600
VACNormal
overload
110%
for
1
minute
-
continued
Size:
P1K1
P1K5
P2K2
P3K0
P3K
7
P4K0
P5K5
P7K5
P11K
P15K
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Max.
input
current
130BA057.10
Continuous
(3
x
525–600
V)
[A]
2.4
2.7
4.1
5.2
-
5.8
8.6
10.4
17.2
20.9
25.4
32.7
39
49
59
78.9
95.3
124.3
Intermittent
(3
x
525–600
V)
[A]
2.7
3.0
4.5
5.7
-
6.4
9.5
11.5
19
23
28
36
43
54
65
87
105
137
Max.
pre-fuses
1)
[A]
10
10
20
20
-
20
32
32
63
63
63
63
80
100
125
160
250
250
Environment:
Estimated
power
loss
at
rated
max.
load
[W]
4)
50
65
92
122
-
145
195
261
300
400
475
525
700
750
850
1100
1400
1500
Weight
enclosure
IP20
[kg]
6.5
6.5
6.5
6.5
-
6.5
6.6
6.6
12
12
12
23.5
23.5
23.5
35
35
50
50
Weight
enclosure
IP21/55
[lb][kg]
13.5
13.5
13.5
13.5
13.5
13.5
14.2
14.2
23
23
23
27
27
27
45
45
65
65
Efficiency
4)
0.97
0.97
0.97
0.97
-
0.97
0.97
0.97
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
Table
8.6
5)
With
brake
and
load
sharing
95/
4/0
General Specifications and ...
VLT
®
HVAC Drive Design Guide
8-6
MG11BB22 - VLT
®
is a registered Danfoss trademark
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...