3.
RFI filter choke.
Typical values are measured at a distance of 3.28 ft. [1 m]
from the unit:
Enclosure
At reduced fan
speed (50%) [dBA]
***
Full fan speed
[dBA]
A2
51
60
A3
51
60
A5
54
63
B1
61
67
B2
58
70
B3
59.4
70.5
B4
53
62.8
C1
52
62
C2
55
65
C3
56.4
67.3
C4
-
-
D1/D3
74
76
D2/D4
73
74
E1/E2*
73
74
**
82
83
F1/F2/F3/F4
78
80
* 425 hp [315kW], 380–480V AC and 600–675 [450–500kW], 525–
690V AC only.
** Remaining E1/E2 power sizes.
*** For D, E and F sizes, reduced fan speed is at 87%, measured
at 200V.
Table 8.16
8.5 Peak voltage on motor
When a transistor in the inverter bridge switches, the
voltage across the motor increases by a du/dt ratio
depending on:
-
the motor cable (type, cross-section, length,
shielded or non-shielded)
-
inductance
The natural induction causes an overshoot U
PEAK
in the
motor voltage before it stabilizes itself at a level
depending on the voltage in the intermediate circuit. The
rise time and the peak voltage U
PEAK
affect the service life
of the motor. If the peak voltage is too high, motors
without phase coil insulation are especially affected. If the
motor cable is short (by a few yards), the rise time and
peak voltage are lower.
If the motor cable is long (328 ft [100 m]), the rise time
and peak voltage increases.
In motors without phase insulation paper or other
insulation reinforcement suitable for operation with
voltage supply (such as a Adjustable frequency drive), fit a
sine-wave filter on the output of the Adjustable frequency
drive.
To obtain approximate values for cable lengths and
voltages not mentioned below, use the following rules of
thumb:
1.
Rise time increases/decreases proportionally with
cable length.
2.
U
PEAK
= DC link voltage x 1.9
(DC link voltage = AC line voltage x 1.35).
3.
dU
/
dt =
0.8 ×
UPEAK
Risetime
Data are measured according to IEC 60034-17.
Cable lengths are in meters.
Adjustable Frequency Drive, P5K5, T2
Cable
length (ft [m])
AC line
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
118.1 [36]
240
0.226
0.616
2.142
164 [50]
240
0.262
0.626
1.908
328 [100]
240
0.650
0.614
0.757
492.1 [150]
240
0.745
0.612
0.655
Table 8.17
General Specifications and ...
VLT
®
HVAC Drive Design Guide
8-22
MG11BB22 - VLT
®
is a registered Danfoss trademark
8
8
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...