Figure 2.39
Using a digital input and 24V as power supply:
Example: The Adjustable frequency drive trips when the
motor temperature is too high.
Parameter set-up:
Set
1-90 Motor Thermal Protection
to
Thermistor Trip
[2]
Set
1-93 Thermistor Source
to
Digital Input 33
[6]
PTC / Thermistor
OFF
ON
+24V
12 13 18
37
32
A
27
19
29
33
B
20
GND
R
<6.6 k Ω >10.8 k Ω
130BA151.11
Figure 2.40
Using a digital input and 10V as power supply:
Example: The Adjustable frequency drive trips when the
motor temperature is too high.
Parameter set-up:
Set
1-90 Motor Thermal Protection
to
Thermistor Trip
[2]
Set
1-93 Thermistor Source
to
Digital Input 33
[6]
PTC / Thermistor
R
OFF
ON
<800 Ω
+10V
130BA152.10
>2.7 kΩ
12 13
18
37
32
27
19
29
33 20
55
50
39 42
53 54
Figure 2.41
Using an analog input and 10V as power supply:
Example: The Adjustable frequency drive trips when the
motor temperature is too high.
Parameter set-up:
Set
1-90 Motor Thermal Protection
to
Thermistor Trip
[2]
Set
1-93 Thermistor Source
to
Analog Input 54
[2]
Do not select a reference source.
Figure 2.42
Input
Digital/analog
Supply Voltage V
Cut-out Values
Threshold
Cut-out Values
Digital
24
< 6.6k
Ω
- > 10.8k
Ω
Digital
10
< 800
Ω
- > 2.7k
Ω
Analog
10
< 3.0k
Ω
- > 3.0k
Ω
Table 2.19
NOTE!
Ensure that the chosen supply voltage follows the specifi-
cation of the thermistor element utilized.
Summary
With the Torque limit feature, the motor is protected for
being overloaded independent of the speed. With the ETR,
the motor is protected for being overheated and there is
no need for any further motor protection. That means
when the motor is heated up, the ETR timer controls how
long the motor may run at that temperature before it is
Introduction to VLT® HVAC D...
VLT
®
HVAC Drive Design Guide
2-44
MG11BB22 - VLT
®
is a registered Danfoss trademark
2
2
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...