2.9.3 EMC Test Results (Emission)
The following test results have been obtained using a system with a Adjustable frequency drive (with options if relevant), a shielded
control cable, a control box with potentiometer, as well as a motor and motor shielded cable.
RFI filter type
Conducted emission.
Maximum shielded cable length.
Radiated emission
Industrial environment
Housing, trades and
light industries
Industrial
environment
Housing, trades and
light industries
Standard
EN 55011 Class
A2
EN 55011 Class
A1
EN 55011 Class B
EN 55011 Class
A1
EN 55011 Class B
H1
1.5–60 hp [1.1–45 kW]
200–240 V
T2
492 ft [150 m]
492 ft [150 m]
164 ft [50 m]
Yes
No
1.5–125 hp [1.1–90 kW]
380–480V
T4
492 ft [150 m]
492 ft [150 m]
164 ft [50 m]
Yes
No
H2
1.5–5 hp [1.1–3.7 kW]
200–240V
T2
16.4 ft [5 m]
No
No
No
No
7.5–60 hp [5.5–45 kW]
200–240V
T2
82 ft [25 m]
No
No
No
No
1.5–10 hp [1.1–7.5 kW]
380–480 V
T4
16.4 ft [5 m]
No
No
No
No
15–125 hp [11–90kW]
380–480 V
T4
82 ft [25 m]
No
No
No
No
150–1350 hp [110–1000
kW] 380–480 V
T4
492 ft [150 m]
No
No
No
No
15–125 hp [11–90 kW]
525–690 V
T7
Yes
No
No
No
No
60–1900 hp [45–1400 kW]
525–690 V
T7
492 ft [150 m]
No
No
No
No
H3
1.5–60 hp [1.1–45 kW]
200–240 V
T2
246 ft [75 m]
164 ft [50 m]
32.8 ft [10 m]
Yes
No
1.5–125 hp [1.1–90 kW]
380–480 V
T4
246 ft [75 m]
164 ft [50 m]
32.8 ft [10 m]
Yes
No
H4
150–1350 hp [110–1000
kW] 380–480 V
T4
492 ft [150 m]
492 ft [150 m]
No
Yes
No
60–550 hp [45–400 kW]
525–690 V
T7
492 ft [150 m]
98 ft [30 m]
No
No
No
15–125 hp [11–90 kW]
525–690 V
T7
No
Yes
No
Yes
No
Hx
1.5–125 hp [1.1–90 kW]
525–600 V
T6
-
-
-
-
-
Table 2.12 EMC Test Results (Emission)
HX, H1, H2 or H3 is defined in the type code pos. 16 - 17 for EMC filters
HX - No EMC filters built in the Adjustable frequency drive (600V units only)
H1 - Integrated EMC filter. Fulfill Class A1/B
H2 - No additional EMC filter. Fulfill Class A2
H3 - Integrated EMC filter. Fulfill class A1/B (Frame size A1 only)
H4 - Integrated EMC filter. Fulfill class A1
Introduction to VLT® HVAC D...
VLT
®
HVAC Drive Design Guide
MG11BB22 - VLT
®
is a registered Danfoss trademark
2-35
2
2
Содержание VLT HVAC Drive FC 100 Series
Страница 10: ...How to Read this Design Gui VLT HVAC Drive Design Guide 1 6 MG11BB22 VLT is a registered Danfoss trademark 1 1...
Страница 56: ...Introduction to VLT HVAC D VLT HVAC Drive Design Guide 2 46 MG11BB22 VLT is a registered Danfoss trademark 2 2...
Страница 126: ...How to Install VLT HVAC Drive Design Guide 5 38 MG11BB22 VLT is a registered Danfoss trademark 5 5...
Страница 136: ...Application Examples VLT HVAC Drive Design Guide 6 10 MG11BB22 VLT is a registered Danfoss trademark 6 6...
Страница 160: ...RS 485 Installation and Set VLT HVAC Drive Design Guide 7 24 MG11BB22 VLT is a registered Danfoss trademark 7 7...