as another example:
Choose the parameter, press [OK], and use the up/down navigation keys keys to scroll through the indexed values. To change the parameter value,
select the indexed value and press [OK]. Change the value by using the up/down keys. Press [OK] to accept the new setting. Press [CANCEL] to abort.
Press [Back] to leave the parameter.
2.1.14 Initialisation to Default Settings
Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par.14-22
)
1.
Select par.14-22
2.
Press [OK]
3.
Select “Initialisation”
4.
Press [OK]
5.
Cut off the mains supply and wait until the display turns off.
6.
Reconnect the mains supply - the frequency converter is now
reset.
7.
Change par.14-22
back to
Normal Operation
.
NB!
Resets parameters selected in Personal Menu with default factory setting.
initialises all except:
par. 8-30
Protocol
to par.15-05
Manual initialisation
1.
Disconnect from mains and wait until the display turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b.
Press [Menu] while power up for LCP 101, Numerical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed according to default settings.
This procedure initializes all except: par.15-00
.
NB!
When you carry out manual initialisation, you also reset serial communication, par.14-50
and fault log settings.
Removes parameters selected in par. 25-00
Pack Controller
.
NB!
After initialization and power cycling, the display will not show any information until after a couple of minutes.
ADAP-KOOL
®
Drive Programming Guide
2 How to Programme
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
29
2