[20]
R407C
[21]
R407A
[22]
R407B
[23]
R410A
[24]
R170
[25]
R290
[26]
R600
[27]
R600a
[28]
R744
[29]
R1270
[30]
R417A
[31]
Isceon 29
20-31 User Defined Refrigerant A1
Range:
Function:
10.0000 N/
A*
[8.0000 - 12.0000 N/A]
Use this parameter to enter the value of coefficient A1 when par. 20-30
Refrigerant
is set to
User
defined
[7].
20-32 User Defined Refrigerant A2
Range:
Function:
-2250.00 N/
A*
[-3000.00 - -1500.00 N/A]
Use this parameter to enter the value of coefficient A2 when par. 20-30
Refrigerant
is set to
User
defined
[7].
20-33 User Defined Refrigerant A3
Range:
Function:
250.000 N/
A*
[200.000 - 300.000 N/A]
Use this parameter to enter the value of coefficient A3 when par. 20-30
Refrigerant
is set to
User
defined
[7].
3.15.5 20-4* Thermostat/Pressostat Function
The Thermostat-Pressostat Function (TPF) can be used to stop and start the compressor when running in closed loop. The TPF monitors and compares
the resulting feedback with the Cut-out value in par.20-41. When the resulting feedback gets below par. 20-41 a stop signal is generated and the
compressor stops. When the resulting feedback gets above the Cut-in value in par. 20-42 the stop signal is removed and the compressor starts again.
The Set-point should be set to a value in between Cut-in and Cut-out.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
152
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3