[39]
Display Text 3
Enables an individual text string to be written, for display in the LCP or to be read via serial com-
munication.
[89]
Date and Time Readout
Displays the current date and time.
[1501]
Running Hours
View the number of running hours of the motor.
[1502]
kWh Counter
View the mains power consumption in kWh.
[1600]
Control Word
View the Control Word sent from the frequency converter via the serial communication port in hex
code.
[1601]
Reference [Unit]
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selected
unit.
[1602]
Reference [%]
[1603]
Status Word
Present status word
[1605]
Main Actual Value [%]
View the two-byte word sent with the Status word to the bus Master reporting the Main Actual Value.
[1609]
Custom Readout
View the user-defined readouts as defined in par.0-30
and par.0-32
.
[1610]
Power [kW]
Actual power consumed by the motor in kW.
[1611]
Power [hp]
Actual power consumed by the motor in HP.
[1612]
Motor Voltage
Voltage supplied to the motor.
[1613]
Frequency
[1614]
Motor Current
Phase current of the motor measured as effective value.
[1615]
Frequency [%]
Motor frequency, i.e. the output frequency from the frequency converter in percent.
[1616]
Torque [Nm]
Present motor load as a percentage of the rated motor torque.
[1617]
Speed [RPM]
Motor speed reference. Actual speed will depend on slip compensation being used (compensation
set in par.1-62
). If not used, actual speed will be the value read in the display
minus motor slip.
[1618]
Motor Thermal
Thermal load on the motor, calculated by the ETR function. See also parameter group 1-9* Motor
Temperature.
[1622]
Torque [%]
Shows the actual torque produced, in percentage.
[1630]
DC Link Voltage
Intermediate circuit voltage in the frequency converter.
[1632]
Brake Energy /s
[1633]
Brake Energy /2 min
[1634]
Heatsink Temp.
Present heat sink temperature of the frequency converter. The cut-out limit is 95 ± 5
°
C; cutting
back in occurs at 70 ± 5
°
C.
[1635]
Inverter Thermal
[1636]
Inv. Nom. Current
Nominal current of the frequency converter
[1637]
Inv. Max. Current
Maximum current of the frequency converter
[1638]
SL Controller State
[1639]
Control Card Temp.
Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a percentage, i.e. the sum of analog/pulse/bus.
[1652]
Feedback [Unit]
Reference value from programmed digital input(s).
[1653]
Digi Pot Reference
View the contribution of the digital potentiometer to the actual reference Feedback.
[1654]
Feedback 1 [Unit]
View the value of Feedback 1. See also par. 20-0*.
[1655]
Feedback 2 [Unit]
View the value of Feedback 2. See also par. 20-0*.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
36
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...