3.14.2 18-1* Fire Mode Log
The log covers the latest 10 faults which have been suppressed by the Fire Mode function. See
par. 24-0*, Fire Mode
. The log can be viewed either via
the below parameters or by pressing the Alarm Log button on the LCP and select Fire Mode Log. It is not possible to reset the Fire Mode Log.
18-10 Fire Mode Log: Event
Range:
Function:
0 N/A*
[0 - 255 N/A]
This parameter contains an array with 10 elements. The number read represent an error code, which
corresponds to a specific alarm. This can be found in the Troubleshooting section in the Design
Guide.
18-11 Fire Mode Log: Time
Range:
Function:
0 s*
[0 - 2147483647 s]
This parameter contains an array with 10 elements. The parameter shows at which time the logged
event occurred. Time is measured in seconds since the first start of the motor.
18-12 Fire Mode Log: Date and Time
Range:
Function:
0 N/A*
[0 - 0 N/A]
This parameter contains an array with 10 elements. The parameter shows at which date and time
the logged event occurred. The function relies on that the actual date and time has been set in par.
0-70
. Note: There is no build in battery back up of the clock. An external back
up must be used, eg the one in the MCB109 Analog I/O option card. See Clock Settings, 0-7*.
3.14.3 18-3* Analog I/O
18-30 Analog Input X42/1
Range:
Function:
0.000 N/A* [-20.000 - 20.000 N/A]
Read out of the value of the signal applied to terminal X42/1 on the Analog I/O Card.
The units of the value shown in the LCP will correspond to the mode selected in par.26-00
18-31 Analog Input X42/3
Range:
Function:
0.000 N/A* [-20.000 - 20.000 N/A]
Read out of the value of the signal applied to terminal X42/3 on the Analog I/O Card.
The units of the value shown in the LCP will correspond to the mode selected in par.26-01
18-32 Analog Input X42/5
Range:
Function:
0.000 N/A* [-20.000 - 20.000 N/A]
Read out of the value of the signal applied to terminal X42/5 on the Analog I/O Card.
The units of the value shown in the LCP will correspond to the mode selected in par.26-02
18-33 Analog Out X42/7 [V]
Range:
Function:
0.000 N/A* [0.000 - 30.000 N/A]
Read out of the value of the signal applied to terminal X42/7 on the Analog I/O Card.
The value shown reflects the selection in par.26-40
18-34 Analog Out X42/9 [V]
Range:
Function:
0.000 N/A* [0.000 - 30.000 N/A]
Read out of the value of the signal applied to terminal X42/9 on the Analog I/O Card.
The value shown reflects the selection in par.26-50
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
143