5-16 Terminal X30/2 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB101 is installed in the frequency converter. Func-
tions are described under 5-1*
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB101 is installed in the frequency converter. Func-
tions are described under 5-1*
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB101 is installed in the frequency converter. Func-
tions are described under 5-1*
3.7.4 5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29. Set the
I/O function for terminal 27 in par. 5-01
Terminal 27 Mode
, and set the I/O function for terminal 29 in par. 5-02
Terminal 29 Mode
. These parameters
cannot be adjusted while the motor is running.
The digital outputs can be programmed with these functions:
[0]
No operation
Default for all digital outputs and relay outputs
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for operation and applies a supply signal on the control board.
[3]
Drive ready / remote control
The frequency converter is ready for operation and is in Auto On mode.
[4]
Stand-by / no warning
The frequency converter is ready for operation. No start or stop command is been given (start/
disable). There are no warnings.
[5]
Running
The motor is running.
[6]
Running / no warning
The output speed is higher than the speed set in par. 1-81
Min Speed for Function at Stop [RPM]
.
The motor is running and there are no warnings.
[8]
Run on reference / no warning
The motor runs at reference speed.
[9]
Alarm
An alarm activates the output. There are no warnings.
[10]
Alarm or warning
An alarm or a warning activates the output.
[11]
At torque limit
The torque limit set in par. 4-16 or par. 1-17 has been exceeded.
[12]
Out of current range
The motor current is outside the range set in par. 4-18.
[13]
Below current, low
The motor current is lower than set in par. 4-50.
[14]
Above current, high
The motor current is higher than set in par. 4-51.
[15]
Out of speed range
The output speed is outside the range set in par. 4-52 and 4-53.
[16]
Below speed, low
The output speed is lower than the setting in par. 4-52.
[17]
Above speed, high
The output speed is higher than the setting in par. 4-53.
[18]
Out of feedback range
The feedback is outside the range set in par. 4-56 and 4-57.
[19]
Below feedback low
The feedback is below the limit set in par. 4-56 Warning Feedback Low.
[20]
Above feedback high
The feedback is above the limit set in par. 4-57
Warning Feedback High
.
[21]
Thermal warning
The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency
converter, the brake resistor, or the thermistor.
[25]
Reverse
Reversing. Logic ‘1’ =
relay activated, 24 V DC when CW rotation of the motor. Logic ‘0’ = relay not
activated, no signal, when CCW rotation of the motor.
[26]
Bus OK
Active communication (no time-out) via the serial communication port.
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
73
3