By setting par. 5-40
Function Relay
to [9] Alarm and par. 5-41
On Delay
, Relay to 40 Sec. the relay will only activate at either a trip lock alarm or an
alarm, which could not be auto-reset. Only the relay output can be used for this; the digital outputs do not have the On Delay feature.
NB!
The motor may start without warning. If the specified number of AUTOMATIC RESETs is reached within 10 minutes, the drive enters
Manual reset [0] mode. After the Manual reset is performed, the setting of par. 14-20 reverts to the original selection. If the number
of automatic resets is not reached within 10 minutes, or when a Manual reset is performed, the internal AUTOMATIC RESET counter
returns to zero.
NB!
Automatic reset will also be active for resetting safe stop function in firmware version < 4.3x.
NB!
The setting in par. 14-20 is disregarded in case of Fire Mode being active (see par. 24-0*, Fire Mode).
14-21 Automatic Restart Time
Range:
Function:
10 s*
[0 - 600 s]
Enter the time interval from trip to start of the automatic reset function. This parameter is active
when par. 14-20
Reset Mode
is set to
Automatic reset
[1] - [13].
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
120
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...