14-04 PWM Random
Option:
Function:
[0] *
Off
No change of the acoustic motor switching noise.
[1]
On
Transforms the acoustic motor switching noise from a clear ringing tone to a less noticeable ‘white’
noise. This is achieved by slightly and randomly altering the synchronism of the pulse width modu-
lated output phases.
3.11.3 14-1* Mains On/Off
Parameters for configuring mains failure monitoring and handling.
14-12 Function at Mains Imbalance
Option:
Function:
Operation under severe main imbalance conditions reduces the lifetime of the motor. Conditions are
considered severe if the motor is operated continuously near nominal load (e.g. a pump or fan
running near full speed).
When a severe mains imbalance is detected:
[0] *
Trip
Select
Trip
[0] to trip the frequency converter.
[1]
Warning
Select
Warning
[1] to issue a warning.
[2]
Disabled
Select
Disabled
[2] for no action.
[3]
Derate
Select
Derate
[3] for derating the frequency converter.
3.11.4 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling and control card self test or initialisation.
14-20 Reset Mode
Select the reset function after tripping. Once reset, the drive can be restarted.
Option:
Function:
[0] *
Manual reset
Select
Manual reset
[0], to perform a reset via [RESET] or via the digital inputs.
[1]
Automatic reset x 1
Select
Automatic reset x 1…x20
[1]-[12] to perform between one and twenty automatic resets after
tripping.
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10]
Automatic reset x 10
[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
Infinite Automatic Reset
Select
Infinite Automatic Reset
[13] for continuous resetting after tripping.
Application Tip:
If par. 14-20 / 14-21 is set to auto-reset after e.g. 30 Sec. this should be taken in consideration if a relay output is set to call for a service technician in
case of an alarm.
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
119
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...