[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
13-03 Reset SLC
Option:
Function:
[0] *
Do not reset SLC
Retains programmed settings in all group 13 parameters (13-*).
[1]
Reset SLC
Resets all group 13 parameters (13-*) to default settings.
3.10.3 13-1* Comparators
Comparators are used for comparing continuous variables (i.e. output frequency, output current, analog input etc.) to fixed preset values. In addition,
there are digital values that will be compared to fixed time values. See explanation in par.13-10
. Comparators are evaluated once
in each scan interval. Use the result (TRUE or FALSE) directly. All parameters in this parameter group are array parameters with index 0 to 5. Select index
0 to programme Comparator 0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [5]
Option:
Function:
Select the variable to be monitored by the comparator.
[0] *
DISABLED
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor current
[5]
Motor torque
[6]
Motor power
[7]
Motor voltage
[8]
DC-link voltage
[9]
Motor thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input AI53
[13]
Analog input AI54
[14]
Analog input AIFB10
[15]
Analog input AIS24V
[17]
Analog input AICCT
[18]
Pulse input FI29
[19]
Pulse input FI33
[20]
Alarm number
[30]
Counter A
[31]
Counter B
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
107
3