6-60 Terminal X30/8 Output
Option:
Function:
[0] *
No operation
[100]
Output frequency
: 0 - 100 Hz, (0-20 mA)
[101]
Reference
: Minimum reference - Maximum reference, (0-20 mA)
[102]
Feedback
: -200% to +200% of par. CL-14
Maximum Reference/Feedb.
, (0-20 mA)
[103]
Motor current
[104]
Torque rel to limit
: 0 - Torque limit (par.4-16
), (0-20 mA)
[105]
Torq relate to rated
: 0 - Motor rated torque, (0-20 mA)
[106]
Power
: 0 - Motor rated power, (0-20 mA)
[107]
Speed
: 0 - Speed High Limit (par.4-13
), (0-20 mA)
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
: 0 - 100%, (0-20 mA)
[114]
Ext. Closed Loop 2
: 0 - 100%, (0-20 mA)
[115]
Ext. Closed Loop 3
: 0 - 100%, (0-20 mA)
[130]
Output freq. 4-20mA
: 0 - 100 Hz
[131]
Reference 4-20mA
: Minimum Reference - Maximum Reference
[132]
Feedback 4-20mA
: -200% to +200% of par. CL-14
Maximum Reference/Feedb.
[133]
Motor cur. 4-20mA
: 0 - Inverter Max. Current (par.16-37
[134]
Torq.% lim 4-20 mA
: 0 - Torque limit (par.4-16
)
[135]
Torq.% nom 4-20mA
: 0 - Motor rated torque
[136]
Power 4-20mA
: 0 - Motor rated power
[137]
Speed 4-20mA
: 0 - Speed High Limit (4-13 and 4-14)
[138]
Torque 4-20mA
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA
: 0 - 100%
[143]
Ext. CL 1 4-20mA
: 0 - 100%
[144]
Ext. CL 2 4-20mA
: 0 - 100%
[145]
Ext. CL 3 4-20mA
: 0 - 100%
[150]
Max Out Fr 4-20 mA
6-61 Terminal X30/8 Min. Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scales the minimum output of the selected analog signal on terminal X30/8. Scale the minimum
value as a percentage of the maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of the
maximum output value and 25% is programmed. The value can never be higher than the corre-
sponding setting in par.6-62
if value is below 100%.
This parameter is active when option module MCB 101 is mounted in the frequency converter.
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
93
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...