20-06 Feedback 3 Source
Option:
Function:
See par.20-00
for details.
[0] *
No function
[1]
Analog input 53
[2]
Analog input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
20-07 Feedback 3 Conversion
Option:
Function:
See par. 20-01
Feedback 1 Conversion
for details.
[0] *
Linear
[1]
Square root
[2]
Pressure to temperature
20-08 Feedback 3 Source Unit
Option:
Function:
See par. 20-02
Feedback 1 Source Unit
for details.
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[170]
psi
[171]
lb/in²
[172]
in WG
[173]
ft WG
20-12 Reference/Feedback Unit
This parameter determines the unit that is used for the setpoint reference and feedback that the PID Controller will use for controlling the output
frequency of the frequency converter.
Option:
Function:
[60] *
°C
[160]
°F
3.15.3 20-2* Feedback & Setpoint
This parameter group is used to determine how the frequency converter’s PID Controller will use the three possible feedback signals to control the output
frequency of the frequency converter. This group is also used to store the three internal setpoint references.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
148
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3