WARNING 97, Stop Delayed:
Stop of the motor has been delayed due to short cycle protection is active.
See parameter group 22-7*
WARNING 98, Clock Fault:
Date and time has not been set or any back up mounted has failed. See
parameter group 0-7*.
WARNING 200, Fire Mode:
The input command Fire Mode is active. See parameter group 24-0*
WARNING 201, Fire M was Active.:
The input command Fire Mode has been active, but now deactivated. See
parameter group 0-7*
WARNING 202, Fire M Limits Exceeded:
One or more warranty voiding alarms have been suppressed during Fire
Mode. See parameter group 0-7*
ALARM 250, New Spare Part:
The power or Switch Mode Power Supply has been exchanged. The fre-
quency converter type code must be restored in the EEPROM. Select the
correct type code in Par 14-23 according to the label on unit. Remember
to select ‘Save to EEPROM’ to complete.
ALARM 251, New Type Code:
The frequency converter has got a new type code.