6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
-1.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage/low current value set in
par.6-20
and par.6-22
.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
Application
Depend-
ent*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par.6-21
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 54. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
6-27 Terminal 54 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog
outputs are used as part of a de-central I/O system (e.g. when not as part of any frequency con-
verter related control functions, but feeding a Building Management System with data).
[0]
Disabled
[1] *
Enabled
3.8.5 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB 101.
6-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-31 V]
Sets the analog input scaling value to correspond to the low reference/feedback value (set in par.
6-34
Term. X30/11 Low Ref./Feedb. Value
6-31 Terminal X30/11 High Voltage
Range:
Function:
10.00 V*
[par. 6-30 - 10.00 V]
Sets the analog input scaling value to correspond to the high reference/feedback value (set in par.
6-35
Term. X30/11 High Ref./Feedb. Value
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Sets the analog input scaling value to correspond to the low voltage value (set in par.6-30
).
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Sets the analog input scaling value to correspond to the high voltage value (set in par.6-31
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
88
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...