8-53 Start Select
Option:
Function:
Select control of the frequency converter start function via the terminals (digital input) and/or via
the fieldbus.
[0]
Digital input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial communication port or fieldbus option.
[2]
Logic AND
Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] *
Logic OR
Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
8-54 Reversing Select
Option:
Function:
Select control of the frequency converter reverse function via the terminals (digital input) and/or
via the fieldbus.
[0] *
Digital input
Activates Reverse command via a digital input.
[1]
Bus
Activates Reverse command via the serial communication port or fieldbus option.
[2]
Logic AND
Activates Reverse command via the fieldbus/serial communication port, AND additionally via one of
the digital inputs.
[3]
Logic OR
Activates Reverse command via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via
the fieldbus.
[0]
Digital input
Activates the set-up selection via a digital input.
[1]
Bus
Activates the set-up selection via the serial communication port or fieldbus option.
[2]
Logic AND
Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one
of the digital inputs.
[3] *
Logic OR
Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
100
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...