5-50 Term. 29 Low Frequency
Range:
Function:
100 Hz*
[0 - 110000 Hz]
Enter the low frequency limit corresponding to the low motor shaft speed (i.e. low reference value)
in par.5-52
Term. 29 Low Ref./Feedb. Value
. Refer to the diagram in this section.
5-51 Term. 29 High Frequency
Range:
Function:
100 Hz*
[0 - 110000 Hz]
Enter the high frequency limit corresponding to the high motor shaft speed (i.e. high reference
value) in par.5-53
Term. 29 High Ref./Feedb. Value
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the low reference value limit for the motor shaft speed [RPM]. This is also the lowest feedback
value, see also par.5-57
Term. 33 Low Ref./Feedb. Value
5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the high reference value [RPM] for the motor shaft speed and the high feedback value, see
also par.5-58
Term. 33 High Ref./Feedb. Value
5-54 Pulse Filter Time Constant #29
Range:
Function:
100 ms*
[1 - 1000 ms]
Enter the pulse filter time constant. The pulse filter dampens oscillations of the feedback signal,
which is an advantage if there is a lot of noise in the system. A high time constant value results in
better dampening but also increases the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
5-55 Term. 33 Low Frequency
Range:
Function:
100 Hz*
[0 - 110000 Hz]
Enter the low frequency corresponding to the low motor shaft speed (i.e. low reference value) in
par.5-57
Term. 33 Low Ref./Feedb. Value
5-56 Term. 33 High Frequency
Range:
Function:
100 Hz*
[0 - 110000 Hz]
Enter the high frequency corresponding to the high motor shaft speed (i.e. high reference value) in
par.5-58
Term. 33 High Ref./Feedb. Value
.
5-57 Term. 33 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the low reference value [RPM] for the motor shaft speed. This is also the low feedback value,
see also par.5-52
Term. 29 Low Ref./Feedb. Value
5-58 Term. 33 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the high reference value [RPM] for the motor shaft speed. See also par.5-53
.
5-59 Pulse Filter Time Constant #33
Range:
Function:
100 ms*
[1 - 1000 ms]
Enter the pulse filter time constant. The low-pass filter reduces the influence on and dampens os-
cillations on the feedback signal from the control.
This is an advantage, e.g. if there is a great amount on noise in the system. This parameter cannot
be adjusted while the motor is running.
3 Parameter Description
ADAP-KOOL
®
Drive Programming Guide
80
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
3
Содержание ADAP-KOOL Drive
Страница 14: ...2 How to Programme ADAP KOOL Drive Programming Guide 14 MG 11 N1 02 VLT is a registered Danfoss trademark 2...
Страница 201: ...ADAP KOOL Drive Programming Guide 3 Parameter Description MG 11 N1 02 VLT is a registered Danfoss trademark 201 3...
Страница 222: ...4 Parameter Lists ADAP KOOL Drive Programming Guide 222 MG 11 N1 02 VLT is a registered Danfoss trademark 4...