[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
26-41 Terminal X42/7 Min. Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale the minimum output of the selected analog signal at terminal X42/7, as a percentage of the
maximum signal level. E.g. if a 0 V (or 0 Hz) is desired at 25% of the maximum output value. Then
programme 25%. Scaling values up to 100% can never be higher than the corresponding setting
in par.26-42
See principle graph for par.6-51
26-42 Terminal X42/7 Max. Scale
Range:
Function:
100.00 %* [0.00 - 200.00 %]
Scale the maximum output of the selected analog signal at terminal X42/7. Set the value to the
maximum value of the voltage signal output. Scale the output to give a voltage lower than 10V at
full scale; or 10V at an output below 100% of the maximum signal value. If 10V is the desired output
current at a value between 0-100% of the full-scale output, programme the percentage value in the
parameter, i.e. 50% = 10V. If a voltage between 0 and 10V is desired at maximum output, calculate
the percentage as follows:
(
10
V
desired
maximum
voltage
)
x
100 %
i.e.
5
V
: 10
V
5
V
× 100 % = 200 %
See principle graph for par.6-52
26-43 Terminal X42/7 Bus Control
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the level of terminal X42/7 if controlled by bus.
26-44 Terminal X42/7 Timeout Preset
Range:
Function:
0.00 %*
[0.00 - 100.00 %]
Holds the preset level of terminal X42/7.
In case of a bus timeout and a timeout function is selected in par.26-50
output will preset to this level.
26-50 Terminal X42/9 Output
Option:
Function:
Set the function of terminal X42/9.
[0] *
No operation
[100]
Output frequency
: 0 - 100 Hz, (0-20 mA)
[101]
Reference
: Minimum reference - Maximum reference, (0-20 mA)
[102]
Feedback
: -200% to +200% of par. CL-14
Maximum Reference/Feedb.
, (0-20 mA)
[103]
Motor current
[104]
Torque rel to limit
: 0 - Torque limit (par.4-16
), (0-20 mA)
[105]
Torq relate to rated
: 0 - Motor rated torque, (0-20 mA)
[106]
Power
: 0 - Motor rated power, (0-20 mA)
[107]
Speed
: 0 - Speed High Limit (par.4-13
), (0-20 mA)
[108]
Torque
ADAP-KOOL
®
Drive Programming Guide
3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
215